Calculator / Where our figures come from
Where our figures come from
Every number this site uses, what it assumes, and where it will be wrong, and who maintains it. The figure printed on your box always beats ours.
Circuit capacity
Capacity is volts times amps, and the working limit applies a 0.8 factor. In North America that factor is the NEC continuous-load rule, which applies to loads running three hours or more. Holiday lighting plainly qualifies.
In 230 volt regions there is no equivalent mandated derate. BS 7671 and AS/NZS 3000 size the circuit to the design current rather than applying a blanket percentage. We still apply the same 0.8 as practical advice, because outlet circuits are shared, and we say so rather than dressing it up as a regulation.
Chain limits
For North America we use 210 watts for 22 AWG cord and 420 watts for 20 AWG, which are the values UL listing conventionally applies to light strings and which manufacturers print on the tag.
For the UK and Ireland we use the BS 1362 plug fuse rating: 690 watts on a 3 amp fuse, 1,150 on a 5 amp, 2,990 on a 13 amp, all at 230 volts. Light sets are normally supplied with a 3 amp fuse.
For Australia and New Zealand, plugs are unfused, so there is no equivalent figure. The values we offer (400, 800 and 1,200 watts) are general cord ratings, and the manufacturer's printed maximum should always be used in preference.
Wattages
Each wattage is a single planning figure taken from the range that manufacturers and lighting retailers quote for that product class, at or near the midpoint, biased upward where the range is wide. The wattage chart prints both, so you can see the figure we apply next to the range it came from. Real products vary by bulb count, spacing and efficiency, and a set bought this year may differ from the same model bought three years ago.
Where a range is wide (inflatables especially, which are mostly fan) we bias toward the upper end, because under-estimating load is the error with consequences.
What we deliberately do not do
We do not calculate anything upstream of the outlet. Breaker sizing, circuit design, conductor selection and anything inside a consumer unit or panel are outside what a web page should be telling you, and in most jurisdictions that work is notifiable.
We also do not give a single global answer to anything. Every calculation asks for your region first, because voltage and wiring practice change the result.
And where sources disagree badly enough that we cannot pick between them, we publish no figure rather than a plausible-looking wrong one. A number that is out by a factor of two is worse than no number, because it is the figure someone uses to decide whether a run is safe to switch on.
Constants used
| Value | Figure | Source of the convention |
|---|---|---|
| Continuous load derate | 0.80 | NEC continuous-load rule; practice elsewhere |
| 22 AWG chain limit | 210 W | UL light-string listing convention |
| 20 AWG chain limit | 420 W | UL light-string listing convention |
| 18 AWG chain limit | 630 W | UL light-string listing convention, commercial C9 sets |
| UK 3 A plug fuse | 690 W | BS 1362 fuse at 230 V |
| UK 5 A plug fuse | 1,150 W | BS 1362 fuse at 230 V |
| UK 13 A plug fuse | 2,990 W | BS 1362 fuse at 230 V |
| AU, NZ and other 230 V flex | 400 / 800 / 1,200 W | General cord ratings, light to heavy duty, with no fused plug to set a figure |
| North American supply | 120 V | Nominal |
| UK, IE, AU, NZ supply | 230 V | Nominal |
| Running-cost defaults | 6 h × 30 days | Placeholder season; overwrite both with your own |
| Default tariff | $0.17 / £0.25 / A$0.33 / 0.20 | Placeholder residential rates per kWh, US / UK / AU / other 230 V |
Sources
- NFPA 70, National Electrical Code — Article 100, 210.19(A)(1), 210.20(A), 210.8(A)(3) — The definition of a continuous load as three hours or more, the 125 percent sizing rule that gives our 0.8 factor, and the GFCI requirement for outdoor receptacles. www.nfpa.org
- UL 588, Seasonal and Holiday Decorative Products — The listing standard for light strings and the source of the 210, 420 and 630 watt chain limits. www.shopulstandards.com
- BS 7671 and BS 1362 — The British wiring regulations and the plug fuse standard behind the 690, 1,150 and 2,990 watt figures. electrical.theiet.org
- AS/NZS 3000 and AS/NZS 3112 — The Australian and New Zealand wiring rules and plug standard — the reason there is no fused-plug figure for that region and no mandated derate. www.standards.org.au
- CSA C22.1:24, Canadian Electrical Code, Part I (26th edition, 2024) — The Canadian code, which shares the 120 volt supply and the arithmetic but not the authority.