Calculator / Working it out in Australia and New Zealand
230 V, unfused plugs, RCDs
Working it out in Australia and New Zealand
Same voltage as the UK, but no fuse in the plug — which changes where the limit sits and what you have to check.
The plug does not protect you here
Australian and New Zealand plugs to AS/NZS 3112 contain no fuse. There is no intermediate protection between your light set and the circuit breaker in the switchboard, which means the only figure limiting a chain is the maximum the manufacturer prints on the set.
Find it and use it. Where a set gives no figure, treat the flex as light duty and keep a run under a few hundred watts — with LED sets that is dozens of sets, so it is rarely a real constraint.
Circuits and headroom
Socket circuits are typically 16 or 20 amps, with older installations on 10. At 230 volts a 10 amp circuit carries 2,300 watts and a 20 amp circuit 4,600 watts, before allowing anything for the rest of the house.
Because the circuit is shared, leave a meaningful margin. A fifth in reserve is a sensible working figure even though no regulation requires it.
Typical Australian and New Zealand limits
| Circuit | Watts at 230 V | With a fifth in reserve |
|---|---|---|
| 10 A | 2,300 W | 1,840 W |
| 16 A | 3,680 W | 2,944 W |
| 20 A | 4,600 W | 3,680 W |
| 32 A | 7,360 W | 5,888 W |
RCD protection and the summer problem
AS/NZS 3000 requires RCD protection on socket circuits, and outdoor lighting is exactly the case it exists for. If you are in an older place without RCDs, a portable RCD is worth the small cost.
Southern hemisphere Christmas brings a second issue northern guides never mention: heat and UV. Sets left up through a run of forty degree days degrade faster than the same product in a European winter, and sun-perished insulation is a real hazard by the second or third season. Inspect flex before you put it up, not after.
Common questions
How many Christmas lights can I run in Australia?
A 10 amp circuit carries 2,300 watts at 230 volts, and a 20 amp circuit 4,600. Leave about a fifth spare for everything else on the circuit.
Are Australian plugs fused?
No. Unlike UK plugs, AS/NZS 3112 plugs contain no fuse, so the maximum number of sets you can join is whatever the manufacturer prints on the packaging.
Do I need an RCD for outdoor lights?
Socket circuits require RCD protection under AS/NZS 3000, and outdoor lighting is precisely the risk it addresses. A portable RCD is a cheap fix for older installations.
Can I leave lights up all year?
It is hard on them. UV and summer heat perish flex and seals faster than a northern winter does, so inspect cables for cracking before reusing sets that have been outside.
Work out your own load
The load calculator checks both limits against your display.